Telephone: 01284 810586
EcoCooling Ltd. on LinkedInFollow Ecocooling on Twitter

ENERGY SAVING & SAFETY

Evaporative Cooling from ecocooling

FORTHCOMING EVENTS:
We regularly attend trade shows and environmental events - any forthcoming events will appear below - we look forward to meeting you there

talk to Ecocoling about environmentally friendly evaporative cooling

 

Data Centre World Conference & Expo 2012
Feb 29th and 1st March
Venue London Olympia

Data centre Dynamics
Local talk – Data Centre Revolution
Hannover Germany – 8th March

NEMEX 2012

22-24th May 2012
Birmingham NEC

The Energy Event 2012
11-12 Sep
NEC Birmingham stand H22

Energy Solutions
10-11 October 2012
Stand G20 London Olympia

 

Alan Beresford
MANAGING DIRECTOR OF ECOCOOLING
is on the CIBSE steering committee for the design of data centre Cooling

Evaporative Cooling Configuration

Whilst it is possible to install the coolers without any modification to the control system there is the possibility to customise the performance using the dip switches contained on the printed circuit board in the control panel.

Evaporative Cooling configuration
Evaporative Cooling configuration

The default settings and their functions are shown below:

Switch Default Function
1 Off Pre Cool Cycle – Allows the pad to wet for 5 minutes before fan starts
2 Off Salinity 1
3 On Salinity 2
4 On Salinity 3
5 Off 24 hr dry cycle – Sets the cooler to dry out completely every 24 hrs
6 Off Off speed 1390 On max speed 1200
7 Off Off speed 1390 On max speed 1000
8 Off Enables complete stop in Auto instead of remaining at speed 1/vent

Notes:

The default salinity setting is 30% bleed which is suitable for most mains water supply. Range of 18% to 56% available.

The spare output on the printed circuit board is available to control a ventilation fan which will run whenever the cooler is operational.

The LED will be display the last alarm condition should one have occurred.

 