Case Studies - Cooling the Bakery

Evaporative cooling in the bakery
Data Centre Cooling with Evaporative Cooling

cooling the data centre

 

Evaporative Cooling in the Data Centre

 

12 down discharge EcoCoolers have been supplied and fitted to 12 Air Handling Units (AHU’s) on the roof of Manor Bakeries, Barnsley to provide cooling for the bakery.

The existing refrigeration based cooling system has been decommissioned and the Packaging Area is now solely cooled using the EcoCooling Evaporative cooling system.

Each EcoCooler can provide upto 40KW of cooling for an electrical input of only 1.2KW, saving both money and carbon emissions.

Following commissioning the system was tested and monitored.

External Ambient = 23C° (warm sunny clear day)

Air temp off cooler = 16.6C°

Air volume through cooler = 4.47m3/s

Present Cooling capacity = 34KW per cooler

Total System capacity = 12 coolers x 34KW = 408 KW

Due to the modular nature of the design it can be expanded as the internal equipment within the area increases, easily coping with any increased heat emissions.